Using power frequency transformer, pure sine wave AC output, adaptive load capacity
★ automatic high-low pressure adjustment function ( AVR ), 145 v ~ 275 v super wide range input, high precision output, fully automatic voltage regulator, can adapt to any adverse voltage environment
Intelligent charging, can adjust the size of charging current according to the size of the battery, fast and reliable, and can improve the life of the battery
★ intelligent liquid crystal display output voltage, frequency, battery capacity, fault, overload, load, etc
★ the user can set the unattended operation by RS232 or USB communication software program, and the automatic timing shutdown function
★ the power supply time may be arbitrarily configured according to different requirements
★ can adapt to any bad electric power environment
★ it can automatically start up in the case of commercial power, and it can be used more widely
★ advanced constant current automatic charging circuit to extend battery life
★ full range of protection, such as battery under - voltage, overload, short circuit protection, etc., is safe and reliable
Technical specifications | |||
Model | FG-B1000 | ||
Nominal capacity | 1000W | ||
The battery voltage | 24V36V / 96V | ||
Size | 405×180×320mm | ||
Packing size | 460×240×380mm | ||
Net weight ( kg ) | 17kg | ||
Gross weight ( kg ) | 18kg | ||
Parameter | |||
Input | Voltage | 145-275VAC | |
Output | Frequency | 45Hz~65Hz | |
| Voltage | 220V±2%( battery mode ) | |
| Frequency | 50Hz±0.5 | |
Output waveform | Pure sine wave | ||
Distortion of output waveform | ≤3% | ||
Charging | 5A-15A | ||
Display | LCD | ||
Switching time | <4ms | ||
Environment | Noise | ≤50dB | |
| Temperature | 0℃~40℃ | |
| Humidity | 10%~90%( no condensation ) | |
Efficiency | ≥80% | ||
Protection | Overload | Overload 110 %, 30 seconds automatic machine shutdown; Overload 120 %, 2 seconds automatic shutdown; Power mode overload does not shut down, the buzzer issued an alarm sound | |
| Short circuit | When the output short circuit, the buzzer Blew, 20 seconds after the machine automatically shut down | |
| Battery | Protection of high and low voltage battery | |
Alarm sound | A | When the city power is working, the machine has no alarm; When the power supply fault, the machine is in the battery working state, the buzzer will call four times per 30 seconds | |
| B | When the battery low voltage secondary alarm, the buzzer is called once per second; Battery mode, the machine fault, the buzzer sounded urgent | |
| C | When overload, the buzzer will beep every second | |
Remarks | Specifications are subject to change without prior notice |